0.75–250 kW · 200–600 V · IP20, IP55 & IP66
The Invertek Optidrive ECO is a variable frequency drive built for fans and pumps, from 0.75 to 250 kW. Energy optimisation, BACnet on board, fire mode and Optiflow multi-pump control are built in, so it runs air handling, building services and pumping stations efficiently and quietly without extra controllers.
Fans and centrifugal pumps use far less power at reduced speed, so matching speed to demand is one of the simplest ways to cut running costs. The Optidrive ECO is designed for exactly that load. Invertek sets it up in two versions: HVAC and building services, and advanced pump control. Supplies covered:
IP20 drives mount in a control panel, in frame sizes 2 to 8 up to 250 kW. IP55 drives mount without a panel, on a wall or in a plant room, in frame sizes 4 to 8 up to 250 kW. IP66 (NEMA 4X) drives are outdoor rated, up to 22 kW at 400 V, with switched versions that add local controls.
For pump applications, Optiflow links up to five drives with RJ45 patch leads to run a pump station in duty, assist and standby without a separate controller. For general machinery, see the Optidrive E3 or, for demanding duties, the Optidrive P2. Our article on the benefits of VFDs explains where the energy savings come from.
| Specification | Optidrive ECO |
|---|---|
| Supply voltage | 200–240 V, 380–480 V, 500–600 V (±10%); single phase at 230 V, three phase at all voltages |
| Supply frequency | 48–62 Hz |
| Power range | 0.75–250 kW |
| Enclosures | IP20, frame sizes 2–5, 6A, 6B and 8; IP55, frame sizes 4–8; IP66 / NEMA 4X, frame sizes 2–4 up to 22 kW (400 V), switched or non-switched |
| Output frequency | 0–250 Hz, 0.1 Hz resolution |
| Overload | 110% for 75 seconds; 150% for 15 seconds in constant torque mode |
| Efficiency | Over 98% |
| Switching frequency | 4–32 kHz effective |
| Control modes | Eco sensorless vector, PM vector, BLDC vector, synchronous reluctance vector |
| Motor types | Induction (IE2–IE3), permanent magnet, BLDC, synchronous reluctance, line start PM |
| Braking | AC flux braking |
| Safe torque off | Built in; TÜV certified to SIL 2 |
| EMC filter | Built in |
| Harmonics | Designed to IEC 61000-3-12 |
| Inputs | 5 programmable (3 digital, 2 analogue/digital), up to 8 with options; motor PTC thermistor input |
| Outputs | 4 programmable (2 analogue/digital, 2 relays), up to 7 with options |
| Auxiliary supplies | 24 V DC 100 mA; 10 V DC 10 mA potentiometer supply |
| Communications | BACnet MS/TP and Modbus RTU built in; BACnet/IP, PROFIBUS DP, PROFINET IO, DeviceNet, EtherNet/IP, EtherCAT and Modbus TCP optional |
| Application features | PID, multi-setpoint, sleep and boost, bidirectional fire mode, load monitoring, multi-pump duty/assist/standby, pump stir |
| Monitoring | Fault log with time stamps, kWh meters, run hours, maintenance interval indicator |
| Keypad | Built-in multi-language text display; optional remote keypad |
| Ambient temperature | IP20: −10 to 50 °C; IP55: −10 to 40 °C (50 °C derated); IP66: −20 to 40 °C (50 °C derated) |
| Altitude | Up to 1,000 m without derating; 2,000 m maximum (UL); 4,000 m maximum (non-UL) |
| Approvals | CE, UKCA, UL, cUL, RCM, EAC |
| Manufacturer's warranty | 36 months as standard, extendable to 5 years |
Specifications from ABB literature (NEMA Motors catalogue, 08/2025). Confirm against the datasheet for your model.
| Supply | Power range |
|---|---|
| 200–240 V single phase | 0.75–7.5 kW (1–10 HP) |
| 200–240 V three phase | 0.75–75 kW (1–100 HP) |
| 380–480 V three phase | 0.75–250 kW |
| 500–600 V three phase | 0.75–110 kW (1–150 HP) |
Specifications from ABB literature (NEMA Motors catalogue, 08/2025). Confirm against the datasheet for your model.
For technical information, brochures and further product details, visit our downloads page.
A fan or centrifugal pump needs much less power at reduced speed, so running it at the speed demand calls for, rather than at full speed with a damper or valve, cuts energy use. The ECO adds energy optimisation, sleep mode and dual setpoints, and shows consumption on its built-in kWh meters. Read more on how Optidrives cut energy use.
Optiflow is the ECO’s built-in multi-pump control. Up to five drives connect with RJ45 patch leads and run as one system in any duty, assist or standby arrangement, with automatic changeover and equal run time. If a pump or the master drive faults, the system reconfigures and keeps running.
Yes. Bidirectional fire mode keeps smoke extraction and stairwell pressurisation fans running for the longest permissible period, and fresh air fans can be reversed for smoke extraction.
They share the same range of sizes and enclosures. The ECO is set up for variable torque fan and pump loads, with HVAC and pump features and BACnet on board. The Optidrive P2 is for constant torque and demanding machinery, with higher overload, closed loop control and hoist mode.
Frame size 8, rated up to 250 kW at 400 V, in IP20 or IP55. It has a built-in DC link choke to reduce harmonics. Read more about the Optidrive frame size 8 range.
The Optidrive ECO user guide is in our download library, with the HVAC and pump brochures.
Send us the order code from the drive label, or the motor power, supply, enclosure and fan or pump duty, for a quote. Call 01924 411921 or email sales@betech.co.uk.
Contact
Betech 100pt Ltd
Four Square Buildings, Thomas Street
Heckmondwike, West Yorkshire, WF16 0LS
Telephone: 01924 411921
Email: sales@betech.co.uk
Opening hours: 8:00 to 17:00